Select the correct wire gauge (AWG) for your AC load and circuit distance
| AWG | Ampacity | Ω / 1000ft (Cu) | Ω / 1000ft (Al) |
|---|
Determine the load current (I = Watts ÷ Voltage for single-phase, or I = Watts ÷ (√3 × V × PF) for 3-phase). Pick an AWG that exceeds this current per NEC ampacity, then confirm voltage drop over the one-way distance stays under 3% for branch circuits or 5% total for feeders.
For 20A at 120V single-phase, 100 ft: 12 AWG meets ampacity but causes ~6% drop. Use 10 AWG copper for ~3.9% drop, or 8 AWG for ~2.4% to stay safely under 3%.
NEC recommends 3% max for branch circuits and 5% for feeders, with a combined maximum of 5% from the service entrance to the farthest outlet.